    <p type="txt_05" class="MEDAPS_txt_05">
      <u>Y-Link</u>
    </p>
    <ul class="MEDAPS_ul1">
      <li>Transmission rates for the redundant master system: <br>9.6&#160;Kbit/s to 12&#160;Mbit/s.</li>
      <li>Bumpless switchover of the redundant PROFIBUS&#160;DP master system's active channel.</li>
      <li>Supports system changes on a SIMATIC S7-400H during operation.</li>
      <li>Diagnostics using LEDs and the user program</li>
    </ul>
    <p type="txt_05" class="MEDAPS_txt_05">
      <u>Y-Coupler</u>
    </p>
    <ul class="MEDAPS_ul1">
      <li>Transmission rates for the lower-level master system (independent of redundant DP master system): <br>187.5&#160;Kbit/s to 12&#160;Mbit/s.</li>
      <li>Electrical isolation between lower-level DP master system and power supply via the coupler.</li>
      <li>Degree of protection IP20</li>
    </ul>
    <h5>Principle of operation</h5>
    <p type="txt_05" class="MEDAPS_txt_05">The Y-Link maps the lower-level DP master system on the redundant PROFIBUS&#160;DP master system as a switched PROFIBUS&#160;DP slave .</p>
    <p type="txt_05" class="MEDAPS_txt_05">The Y-Coupler and the lower-level DP master system form an independent bus system and operate decoupled from the redundant bus system.</p>
    <p type="txt_05" class="MEDAPS_txt_05">The Y-Link as a DP slave on the redundant DP master system acts as a proxy for the stations on the lower-level DP master system with regard to data.</p>
    <h5>Configuration</h5>
    <p type="txt_05" class="MEDAPS_txt_05">The Y-Link can be configured with STEP&#160;7 as of Version 5.2. It is not necessary to configure the Y-Coupler.</p>
    <p type="txt_05" class="MEDAPS_txt_05">When STEP&#160;7 calculates the bus parameters, the stations connected on the lower-level DP master system as well as the Y-Link itself are taken into account.</p>
    <p type="txt_05" class="MEDAPS_txt_05">
      <u>Parameter assignment for the DP slaves</u>
    </p>
    <p type="txt_05" class="MEDAPS_txt_05">The redundant DP master system assigns the parameters for the DP slaves in the lower-level DP master system via the Y-Link.</p>