{\rtf1\ansi\ansicpg1252\uc0\deff0{\fonttbl {\f0\fswiss\fcharset0\fprq2 Arial;} {\f1\froman\fcharset2\fprq2 Symbol;}} {\colortbl;\red0\green0\blue0;\red255\green255\blue255;} {\info{\*\hlinkbase e:\\Medaps\\CA01_Generate\\export\\CA01_ENG_INT_IK_05102004\\rtf\\}{\comment TX_RTF32 8.0.300.500}} \deftab708\paperw15309\paperh16840\margl1134\margt1134\margr3430\margb1338\pard\sb100\plain\f0\fs18 The 313C CPU includes:\par\pard\fi-284\li284\sb60\tx284\plain\f1\fs18 \'b7\plain\f0\fs18\tab Microprocessor;\line the processor reaches a processing time of 100 - 200 ns per binary instruction\par\plain\f1\fs18 \'b7\plain\f0\fs18\tab Extensive memory capacity;\line 32 KB fast RAM (corresponds to about 10 K instructions) for execution-relevant program parts provide user programs with sufficient space;\line Micro memory cards (8 MB max.) as load memory for the program allow additional projects to be stored (including symbols and comments) in the CPU.\par\plain\f1\fs18 \'b7\plain\f0\fs18\tab Flexible expansion;\line max. 31 modules (4-tier configuration)\par\plain\f1\fs18 \'b7\plain\f0\fs18\tab Interface with multipoint capability (MPI);\line the integrated MPI interface can establish up to 8 connections simultaneously to an S7-300/400 or to a programming device, PC or OP. Among these connections, one is always reserved for PG and another for OP. The MPI makes it possible to set up a simple network with a maximum of 16 CPUs via "global data communication".\par\plain\f1\fs18 \'b7\plain\f0\fs18\tab Integrated inputs/outputs\line 24 digital inputs (all usable for interrupt handling) and 16 digital outputs, as well as 4 analog inputs and 2 analog outputs for current/voltage signals and one additional input for temperature measurement, are available on the CPU\~313C.\par\pard\par }